الأحد، 5 يناير 2014

Counters
A counter is a simple device intended to do one simple thing - count. Using them, however, can sometimes be a challenge because every manufacturer (for whatever reason) seems to use them a different way. Rest assured that the following information will let you simply and easily program anybody's counters.
What kinds of counters are there? Well, there are up-counters (they only count up 1,2,3...). These are called CTU,(count up) CNT,C, or CTR. There are down counters (they only count down 9,8,7,...). These are typically called CTD (count down) when they are a separate instruction. There are also up-down counters (they count up and/or down 1,2,3,4,3,2,3,4,5,...) These are typically called UDC(up-down counter) when they are separate instructions.
Many manufacturers have only one or two types of counters but they can be used to count up, down or both. Confused yet? Can you say "no standardization"? Don't worry, the theory is all the same regardless of what the manufacturers call them. A counter is a counter is a counter...
To further confuse the issue, most manufacturers also include a limited number of high-speed counters. These are commonly called HSC (high-speed counter), CTH (CounTer High-speed?) or whatever.
Typically a high-speed counter is a "hardware" device. The normal counters listed above are typically "software" counters. In other words they don't physically exist in the plc but rather they are simulated in software. Hardware counters do exist in the plc and they are not dependent on scan time.
A good rule of thumb is simply to always use the normal (software) counters unless the pulses you are counting will arrive faster than 2X the scan time. (i.e. if the scan time is 2ms and pulses will be arriving for counting every 4ms or longer then use a software counter. If they arrive faster than every 4ms (3ms for example) then use the hardware (high-speed) counters. (2xscan time = 2x2ms= 4ms)
To use them we must know 3 things:
  1. Where the pulses that we want to count are coming from. Typically this is from one of the inputs.(a sensor connected to input 0000 for example)
  2. How many pulses we want to count before we react. Let's count 5 widgets before we box them, for example.
  3. When/how we will reset the counter so it can count again. After we count 5 widgets lets reset the counter, for example.
When the program is running on the plc the program typically displays the current or "accumulated" value for us so we can see the current count value.
Typically counters can count from 0 to 9999, -32,768 to +32,767 or 0 to 65535. Why the weird numbers? Because most PLCs have 16-bit counters. We'll get into what this means in a later chapter but for now suffice it to say that 0-9999 is 16-bit BCD (binary coded decimal) and that -32,768 to 32767 and 0 to 65535 is 16-bit binary.
Here are some of the instruction symbols we will encounter (depending on which manufacturer we choose) and how to use them. Remember that while they may look different they are all used basically the same way. If we can setup one we can setup any of them.
1st counter symbol
In this counter we need 2 inputs.
One goes before the reset line. When this input turns on the current (accumulated) count value will return to zero.
The second input is the address where the pulses we are counting are coming from.
For example, if we are counting how many widgets pass in front of the sensor that is physically connected to input 0001 then we would put normally open contacts with the address 0001 in front of the pulse line.
Cxxx is the name of the counter. If we want to call it counter 000 then we would put "C000" here.
yyyyy is the number of pulses we want to count before doing something. If we want to count 5 widgets before turning on a physical output to box them we would put 5 here. If we wanted to count 100 widgets then we would put 100 here, etc. When the counter is finished (i.e we counted yyyyy widgets) it will turn on a separate set of contacts that we also label Cxxx.
Note that the counter accumulated value ONLY changes at the off to on transition of the pulse input.
Counter ladder
Here's the symbol on a ladder showing how we set up a counter (we'll name it counter 000) to count 100 widgets from input 0001 before turning on output 500. Sensor 0002 resets the counter.
Below is one symbol we may encounter for an up-down counter. We'll use the same abbreviation as we did for the example above.(i.e. UDCxxx and yyyyy)
Up/down counter symbol
In this up-down counter we need to assign 3 inputs. The reset input has the same function as above. However, instead of having only one input for the pulse counting we now have 2. One is for counting up and the other is for counting down. In this example we will call the counter UDC000 and we will give it a preset value of 1000. (we'll count 1000 total pulses) For inputs we'll use a sensor which will turn on input 0001 when it sees a target and another sensor at input 0003 will also turn on when it sees a target. When input 0001 turns on we count up and when input 0003 turns on we count down. When we reach 1000 pulses we will turn on output 500. Again note that the counter accumulated value ONLY changes at the off to on transition of the pulse input. The ladder diagram is shown below.
Up/down counter ladder
Click here view the animation!and view the animation to really learn!
One important thing to note is that counters and timers can't have the same name (in most PLCs). This is because they typically use the same registers. We haven't learned about timers yet but you might make a note of this for future reference because it's pretty important.
Well, the counters above might seem difficult to understand but they're actually quite easy once we get used to using them. They certainly are an essential tool. They are also one of the least "standardized" basic instructions that we will see. Howeve

0 التعليقات: